Nominal Voltage 24 VDC
Type TMR, SupervisedNon-Supervised DO
Output Signals 32, commoned
Voltage Range 16-32 VDC
Maximum Voltage 36 VDC
Voltage Drop 2. , typical
Power Module Load 13 watts
Current Ratings, Maximum 1.7A per point 7A surge per 10 ms
Minimum Required Load 10 mA
Load Leakage 4 mA maximum
Fuses (on Field Termination) na—self-protecting
Point Isolation 1,500 VDC
Diagnostic Indicators
On or Off State 1 per point
Module Status PASS, FAULT, LOAD, ACTIVE
Field Alarm LOAD (1 per point)
Color Code Dark blue
MFG TRICONEX
TRICONEX 3625 DIGITAL 24VDC OUTPUT MODULE INVENSYS SYSTEM
Origin Made in USA
额定电压24伏直流电
类型咯,监督/非做
输出信号32,常见
电压范围至少需要补充16至32伏直流
较大电压36 VDC
电压降< 2.8 VDC @ 1.7,典型
电源模块加载< 13瓦
当前的评级,较大1.7每点7每10毫秒
较低要求负载10马
负载漏4马较大
保险丝(字段终止)n / a-self-protecting
1500点隔离直流
诊断指标
打开或关闭状态1每点
模块状态通过断层、加载、活跃
现场报警负载(每点1)
深蓝色的颜色代码
生产厂:TRICONEX
3805E Triconex 3805E Enhanced Analog Output PLC Module 3805E
0 Comments/in Invensys, Triconex Safety Systems /
3805E Triconex 3805E Enhanced Analog Output PLC Module 3805E
Model Number 3805E/3805H
Type TMR, AO
Output current range 4-20 mA output (+6% overrange)
Number of points 8 output
Isolated points No, commoned return, DC coupled
Resolution 12 bits
Output Accuracy <0.25% (in range of 4-20 mA) of
FSR (0-21.2 mA), from 32° to 140°
F (0° to 60° C)
External loop power +42.5 VDC, maximum
(reverse voltage protected) +24 VDC, nominal
Output loop power
requirements
Load (Ohms) Loop power required
250 > 20 VDC (1 amp minimum)
500 > 25 VDC (1 amp minimum)
750 > 30 VDC (1 amp minimum)
1000 > 35 VDC (1 amp minimum)
Over-range protection +42.5 VDC, continuous
Switch time on leg failure < 10 ms, typical
Diagnostic Indicators
Module status PASS, FAULT, ACTIVE,
(one each per module) LOAD, PWR1, PWR2
Color code Pea green
MFG: TRICONEX, Made in USA
Tags: 3805E, 3805E Module, 3805E Triconex, Triconex 3805E, Triconex 3805E Enhanced Analog Output PLC Module 3805 e Triconex 3805 e增强模拟输出PLC模块3805 e
0评论/英维思集团,Triconex安全系统/
3805 e Triconex 3805 e增强模拟输出PLC模块3805 e
型号3805 e / 3805 h
类型咯,AO
输出电流范围4 - 20毫安输出(+**量程的6%)
8点输出
孤立点不,常见的回报,直流耦合
12位分辨率
输出精度小于0.25%(4 - 20毫安的范围内)
FSR(0 - 21.2 mA),从32°- 140°
60°F(0°C)
外部循环功率+ 42.5 VDC,较大
(反向电压保护)+ 24 VDC,名义
循环输出功率
需求
加载(欧姆)循环功率要求
250 > 20 VDC(1安培较低)
500 > 25 VDC(1安培较低)
750 > 30 VDC(1安培较低)
1000 > 35 VDC(1安培较低)
整个范围保护+ 42.5 VDC,连续的
开关时间腿< 10 ms,典型的失败
诊断指标
模块状态,错,活跃,
(每个模块)一个每个负载,PWR1 PWR2
颜色代码淡绿色
生产厂:TRICONEX,美国制造